PSI/II Live-Front Pad-Mounted Switchgear
The Federal Pacific PSI/II is a live-front pad-mounted switchgear designed for underground medium-voltage distribution systems requiring the switching ratings and performance normally found only in metal-enclosed switchgear. Available in 15 pre-engineered switching configurations, the PSI/II covers radial feed, loop feed, and manual primary-selector switching applications with three-time fault-close ratings and proven Auto-Jet switching technology.
Available in 15kV and 25kV (UL Listed) as the PSI/II design, with 35kV available as the larger PSI design (not UL Listed), the product line is well suited for near-substation high fault-current applications, mid-point loop switching, and distant end-point standard fault-current installations.
Technical Overview
The PSI/II enclosure features the same heavy-gauge construction as the PSE with the addition of GPO-3 fiberglass barriers for live-front personnel protection.
- Low-profile 11-gauge pickled and oiled steel, all-welded construction with cross-kinked roof to eliminate standing water.
- Removable NEMA Class GPO-3 non-hygroscopic fiberglass reinforced polyester barriers for live-front phase isolation and personnel protection.
- 100% X-rayed cycloaliphatic epoxy insulators for superior dielectric reliability.
- Stainless steel hinges and hinge pins with padlockable self-resetting three-point auto-latch door security system.
- Stainless steel door-handle covers and switch operating pockets.
- Electrostatically deposited baked powder epoxy primer and polyester topcoat finish meeting ANSI C57.12.28 requirements.
- Meets IEEE C37.74 requirements including three-time fault-closing on switches and fuse mountings. UL Listed at 15kV and 25kV.
Typical Applications
The PSI/II is specified for utility underground distribution systems requiring live-front switching performance at ratings normally associated with metal-enclosed switchgear.
Utilities
Near-substation and mid-point loop switching for underground radial and loop distribution systems with high fault-current requirements, including primary-selector switching applications.
Standard PSI/II
- 15 pre-engineered configurations available as UL Listed standard units.
- Three-time fault-close ratings with Auto-Jet switching for near-substation and mid-point loop applications.
- Radial feed, loop feed, and manual primary-selector switching configurations available.
- Special configurations and designs available upon request.
PSI/II 6-Compartment
- Available as UL Listed at 15kV and 25kV.
- Up to five 600A live-front switch compartments and up to five 200A live-front fuse compartments in a single enclosure.
- Bus-tie configurations available.
- Reduces land space requirements compared to two standard four-compartment units.
- Manual, automatic source transfer, and SCADA-controlled configurations available.
- For 8-compartment designs, consult factory.
Documentation and Resources
Access technical specifications and installation manuals for the PSI/II Live-Front Pad-Mounted Switchgear.
Lifecycle Support
Custom Engineering
Site-specific configuration support for tailored layouts and integration with existing infrastructure.
Installation Support
Technical guidance for proper equipment placement, cable termination, and system interconnection.
Engineered for Performance
Federal Pacific and its divisions bring decades of engineering experience and application knowledge to every PSI/II project. Teams work closely with engineers, contractors, and facility operators to deliver solutions configured for the specific voltage, capacity, and operational requirements of each application, avoiding the delays and limitations of a one-size-fits-all approach.
Discuss Your Application Requirements